(C) Motor constant parameters
Parameters
5 - 302
Performing tuning
●
In the PU operation mode, press FWD/REV key on the operation panel.
For External operation, turn ON the start command (STF signal or STR signal). Tuning will start.
NOTE
Before performing tuning, check the monitor display of the operation panel or the parameter unit
if the inverter is in the state ready for tuning. (Refer to (2) below.) Turning ON the start command
while tuning is unavailable starts the motor.
NOTES
Satisfy the required inverter start conditions to start offline auto tuning. For example, stop the
input of MRS signal.
To force tuning to end, use the MRS or RES signal or press STOP/RESET key on the operation panel.
(Turning the start signal (STF signal or STR signal) OFF also ends tuning.)
During offline auto tuning, only the following I/O signals are valid (initial value):
●
Input terminals <effective signals>: STP (STOP), OH, MRS, RT, RES, STF, STR, S1 and S2
●
Output terminals: RUN, OL, IPF, FM/CA, AM, A1B1C1 and SO
When the rotation speed and the output frequency are selected for terminals FM/CA and AM, the
progress status of offline auto tuning is output in fifteen steps from FM/CA and AM.
Do not perform ON/OFF switching of the Second function selection (RT) signal during offline auto
tuning. Auto tuning will not be performed properly.
When the offline auto tuning is selected (Pr. 96 "Auto tuning setting/status" = "101"), the motor
rotates. Take caution and ensure the safety.
Since the Inverter running (RUN) signal turns ON when tuning is started, pay close attention espe-
cially when a sequence which releases a mechanical brake by the RUN signal has been designed.
When executing offline auto tuning, input the run command after switching ON the main circuit
power (R/L1, S/L2, T/L3) of the inverter.
While Pr. 79 "Operation mode selection" = "7", turn the PU operation external interlock (X12) signal
ON to tune in the PU operation mode.
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......