(A) Application parameters
Parameters
5 - 348
576
A622
Output interruption
detection level
0 Hz
0 to 590 Hz
Set the frequency at which output interruption is
performed.
577
A623
Output interruption
cancel level
1000%
900 to 1100%
Level at which the PID output suspension function is
released.
Set "Pr. 577 – 1000%".
609
A624
PID set point/deviation
input selection
2
1
Input of set point, deviation value from terminal 1
2
Input of set point, deviation value from terminal 2
3
Input of set point, deviation value from terminal 4
4
Input of set point, deviation value via CC-Link
communication
5
Input of set point, deviation value by PLC function
610
A625
PID measured value input
selection
3
1
Terminal 1 input
Direct input of the
measured value
2
Terminal 2 input
3
Terminal 4 input
4
CC-Link communication
input
5
PLC function input
101
Terminal 1 input
Input of the square root
of the measured value
102
Terminal 2 input
103
Terminal 4 input
104
CC-Link communication
input
105
PLC function input
1015
A607
Integral stop selection at
limited frequency
0
0
Integral stopped at limited frequency, integral
cleared during output interruption
1
Integral continued at limited frequency, integral
cleared during output interruption
10
Integral stopped at limited frequency, integral
stopped during output interruption
11
Integral continued at limited frequency, integral
stopped during output interruption
1370
A442
Detection time for PID
limiting operation
0 s
0 to 900 s
Set the time from when the measured value input
exceeds the Pr. 131 or Pr. 132 setting until the FUP or
FDN signal is output.
1460
A683
PID multistage set point 1
9999
0 to 100%
Seven set points can be set according to the
combination of the PDI1, PDI2, and PDI3 signals.
9999: Not selected
1461
A684
PID multistage set point 2
1462
A685
PID multistage set point 3
1463
A686
PID multistage set point 4
1464
A687
PID multistage set point 5
1465
A688
PID multistage set point 6
1466
A689
PID multistage set point 7
Pr.
Name
Initial
value
Setting range
Description
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......