(A) Application parameters
Parameters
5 - 434
●
When "1" is set in Pr. 415 "Inverter operation lock mode setting", the inverter can be operated only
when the sequence program is running. By changing the PLC program status from RUN to STOP
during inverter operation, the motor decelerates to stop.
To stop the inverter operation at the STOP status of the PLC program while performing auto
operation using SD1148 (or SM1200 to 1211) of the PLC program, set Pr. 415 = "1".
●
For reading or writing sequence programs, use FR Configurator2 on the personal computer
connected to the inverter via RS-485 communication or USB. (When Pr. 414
≠
"0", sequence
programs can be read from or written to FR Configurator2.)
NOTE
For the details of the PLC function, refer to the PLC Function Programming Manual and the
Instruction Manual of FR Configurator2.