Control circuit
Installation and wiring
2 - 56
FR-F820-00770(18.5K) or higher, FR-F840-00470(22K) or higher
Remove the upper screws.
Remove the lower screws.
Pull the jumper toward you to remove.
Connect the separate power supply cable for the control circuit to
the upper terminals (R1/L11,
S1/L21)
.
I002379E
Fig. 2-40:
Detailed view and positions of the terminals
NOTES
When using separate power supplies, always remove the jumpers across terminals R/L1 and R1/
L11 and across S/L2 and S1/L21. The inverter may be damaged if the jumpers are not removed.
The voltage should be the same as that of the main control circuit when the control circuit power
is supplied from other than the input side of the MC.
The power capacity necessary when separate power is supplied from R1/L11 and S1/L21 differs
according to the inverter capacity.
If the main circuit power is switched OFF (for 0.1 s or more) then ON again, the inverter is reset and
a fault output will not be held.
R1/L11
S1/L21
R/L1 S/L2 T/L3
R1/L11 S1/L21
MC
Main power supply
FR-F820-00770(18.5K) to
01250(30K)
FR-F840-00470(22K),
00620(30K)
Power supply
terminal block for
the control circuit
FR-F820-01540(37K)
FR-F840-00770(37K)
FR-F820-01870(45K) or higher
FR-F840-00930(45K) or higher
Power supply terminal block
for the control circuit
Power supply terminal
block for the control
circuit
Inverter
Power supply capacity
FR-F820-00630(15K) or lower
FR-F840-00380(18.5K) or lower
60 VA
FR-F820-00770(18.5K) or higher
FR-F840-00470(22K) or higher
80 VA
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......