(T) Multi-Function Input Terminal Parameters
Parameters
5 - 270
●
There are three methods to adjust the stall prevention operation level setting voltage (current)
bias and gain.
( Method to adjust arbitrary point with application of a voltage (current) between terminals 1
and 5 (4 and 5). Refer to page 5-264.
Method to adjust arbitrary point without application of a voltage (current) between terminals
1 and 5 (4 and 5). Refer to page 5-265.
Method to adjust only stall prevention operation level without adjusting voltage (current).
Refer to page 5-266.
Analog input display unit changing (Pr. 241)
●
The analog input display unit (%/V/mA) for analog input bias and gain calibration can be changed.
●
Depending on the terminal input specification set to Pr. 73 and Pr. 267, the display units of C17
(Pr. 919), C19 (Pr. 920), C39 (Pr. 932), and C41 (Pr. 933) will change as shown below.
NOTE
Always calibrate the input after changing the voltage/input signal with Pr. 73, Pr. 267, and the volt-
age/current input selection switch.
Analog command
(terminals 1 and 4)
(Depends on Pr. 73, Pr. 267)
Pr. 241 = 0 (initial value)
Pr. 241 = 1
0 to 5 V input
0 to 5 V
➔
0 to 100% (0.1%) display
0 to 100%
➔
0 to 5 V (0.01 V) display
0 to 10 V input
0 to 10 V
➔
0 to 100% (0.1%) display
0 to 100%
➔
0 to 10 V (0.01 V) display
0 to 20 mA input
0 to 20 mA
➔
0 to 100% (0.1%) display
0 to 100%
➔
0 to 20 mA (0.01 mA)
Tab. 5-121:
Units when displaying the set value
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......