(T) Multi-Function Input Terminal Parameters
Parameters
5 - 254
5.9.2
Analog input terminal (terminal 1, 4) function assignment
The analog input terminal 1 and terminal 4 functions are set and changeable with parameters.
●
Concerning terminal 1 and terminal 4 used for analog input, the frequency (speed) command,
stall prevention operation level input, and other similar commands are usable. The functions
available are different depending on Pr. 868 "Terminal 1 function assignment", Pr. 858 "Terminal 4
function assignment" as shown in the table below.
Invalid when Pr. 868 = "4"
Parameters referred to
Pr. 22
Stall prevention operation level
=>
Pr. 125
Terminal 2 frequency setting gain frequency
=>
Pr. 126
Terminal 4 frequency setting gain frequency
=>
Pr. 252, Pr. 253
Override bias/gain
=>
Pr. 561
PTC thermistor protection level
=>
Pr. 858
Terminal 4 function assignment
=>
Pr. 868
Terminal 1 function assignment
=>
Pr.
Name
Initial value
Setting range
Description
868
T010
Terminal 1 function assignment
0
0, 4, 9999
Select the terminal 1 function.
(Refer to the table below.)
858
T040
Terminal 4 function assignment
0
0, 4, 9999
Select the terminal 4 function.
(Refer to the table below.)
Setting value
Terminal 1 function (Pr. 868)
Terminal 4 function (Pr. 858)
0
(initial value)
Frequency setting auxiliary
Frequency command (AU signal-ON)
4
Stall prevention operation level input
Stall prevention operation level input
9999
⎯
⎯
—: No function
Tab. 5-112:
Functions of terminals 1 and 4 depending on Pr. 858/868
NOTE
When Pr. 868 = "4" (stall prevention), the terminal 4 function is enabled whether the AU terminal is
turned ON/OFF.
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......