(T) Multi-Function Input Terminal Parameters
Parameters
5 - 264
Frequency setting voltage (current) bias/gain adjustment method
Adjust any point with application of a voltage (current) between terminals 2 and 5 (4 and 5).
(Frequency setting gain adjustment example)
Operation
Screen at power-ON
The monitor display appears.
Changing the operation mode
Press
to choose the PU operation mode. [PU] indicator is lit.
Parameter setting mode
Press
to choose the parameter setting mode. (The parameter number read previously appears.)
Calibration parameter selection
Turn
until
appears. Press
to display
.
"
Selecting the parameter number
Turn
to choose
C4 (Pr. 903) "Terminal 2 frequency setting gain" for the terminal 1.
and
C7 (Pr. 905) "Terminal 4 frequency setting gain" for the terminal 4.
!
Analog voltage (current) display
Press
to display the analog voltage (current) % currently applied to the terminal 1 (4).
Do not touch
until calibration is completed.
Voltage (current) application
Apply a 5 V (20 mA). (Turn the external potentiometer connected across terminals 1 and 5 (terminals 4 and 5) to a
desired position.)
&
Setting completed
Press
to enter the setting. The analog voltage (current) % and
(
) flicker alternately.
Press
to read another parameter.
Press
to return to the
display.
Press
twice to show the next parameter.
Tab. 5-116:
Bias and gain adjustment by application of an reference signal
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......