(C) Motor constant parameters
Parameters
5 - 320
●
Set a given value as the motor constant parameter. The displayed increments of the read motor
constants can be changed with Pr. 684 "Tuning data unit switchover".
For the FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.
For the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
First
motor
Pr.
Second
motor
Pr.
Name
Pr. 684 = 0 (initial value)
Pr. 684 = 1
Initial
value
Setting
range
Setting in-
crements
Range indication
Unit
indication
90
458
Motor constant (R1)
0 to ***,
9999
1
0 to 50 Ω, 9999
0.001 Ω
9999
0 to 400 mΩ, 9999
0.01 mΩ
92
460
Motor constant (L1)/
d-axis inductance
(Ld)
0 to 500 mH, 9999
0.01 mH
0 to 50 mH, 9999
93
461
Motor constant (L2)/
q-axis inductance
(Lq)
0 to 500 mH, 9999
0.01 mH
0 to 50 mH, 9999
706
738
Induced voltage
constant (phi f )
0 to 5000 mV/s/rad,
9999
0.1 mV/
(rad/s)
859
860
Torque current/
Rated PM motor
current
0 to 500 A, 9999
0 to 3600 A, 9999
0.1 A
Tab. 5-154:
Parameter setting ranges
NOTES
As the motor constants measured in the offline auto tuning have been converted into internal
data (****), refer to the following setting example when making setting:
Setting example:
To slightly increase Pr. 90 value (5%)
If Pr. 90 = "2516" is displayed
The value can be calculated with "2516 × 1.05 = 2641.8". Therefore set Pr. 90 = "2642".
(The value displayed has been converted into a value for internal use. Hence, simple addition of a
given value to the displayed value has no significance)
Setting "9999" disables the tuning data. The MM-EFS/MM-THE4 constant is used for the IPM motor
MM-EFS/MM-THE4, and the inverter internal constant is used for a PM motor other than MM-EFS/
MM-THE4.
Parameters referred to
Pr. 9
Electronic thermal O/L relay
=>
Pr. 71
Applied motor
=>
Pr. 178 to Pr. 189
(input terminal function selection)
=>
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......