(E) Environment setting parameters
Parameters
5 - 68
5.4.10
Multiple rating setting
Two rating types of different rated current and permissible load can be selected. The optimal inverter
rating can be chosen in accordance with the application, enabling equipment size to be reduced.
Changing the parameter initial values and setting ranges
●
When inverter reset and all parameter clear are performed after setting Pr. 570, the parameter
initial values are changed according to each rating, as shown below.
The rated current and motor capacity differ depending on the inverter capacity. Refer to the
inverter rated specifications (page 8-1).
Pr.
Name
Initial value
Setting
range
Description (overload current rating,
surrounding air temperature)
FM
CA
570
E301
Multiple rating setting
1
0
0
SLD rating
110% 60 s, 120% 3 s (inverse-time
characteristics)
Surrounding air temperature 40 °C
1
LD rating
120% 60 s, 150% 3 s (inverse-time
characteristics)
Surrounding air temperature 50 °C
Pr.
Name
Pr. 570 setting
Refer to
0
1
9
Electronic thermal O/L relay
SLD rated current
LD rated current
22
Stall prevention operation level
110%
120%
48
Second stall prevention operation level
110%
120%
56
Current monitoring reference
LD rated current
148
Stall prevention level at 0 V input
110%
120%
149
Stall prevention level at 10 V input
120%
150%
150
Output current detection level
110%
120%
165
Stall prevention operation level for restart
110%
120%
557
Current average value monitor signal output
reference current
LD rated current
874
OLT level setting
110%
120%
893
Energy saving monitor reference (motor capacity)
SLD rated motor
LD rated motor
Tab. 5-26:
Influence of Pr. 570 on other parameters
NOTES
When Pr. 570 = "0" (SLD rating), carrier frequency automatic reduction is enabled regardless of the
setting in Pr. 260 "PWM frequency automatic switchover".
Parameters referred to
Pr. 260
PWM frequency automatic switchover
=>
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......