(M) Monitor display and monitor output signal
Parameters
5 - 206
5.8.3
Monitor display selection for terminals FM/CA and AM
The monitored statuses can be output as the following items: analog voltage (terminal AM), pulse
train (terminal FM) for the FM-type inverter, analog current (terminal CA) for the CA-type inverter.
The signal (monitored item) to be output to terminal FM/CA and terminal AM can be selected.
FR-F820-02330(55K) or lower, FR-F840-01160(55K) or lower.
FR-F820-03160(75K) or more, FR-F840-01800(75K) or more.
Function assigned to Pr. 185 "JOG terminal function selection".
Valid only for the FM type inverters.
Pr.
Name
Initial value
Setting range
Description
FM
CA
54
M300
FM/CA terminal function
selection
1
(output
frequency)
1 to 3, 5 to 14, 17, 18,
21, 24, 34, 50, 52, 53,
61, 62, 67, 69, 70, 85,
87 to 90, 92, 93, 95,
98
Select the monitored item to be
output to the terminal FM and
terminal CA.
158
M301
AM terminal function selection
1 to 3, 5 to 14, 17, 18,
21, 24, 34, 50, 52 to
54, 61, 62, 67, 69, 70,
86 to 96, 98
Select the monitored item to be
output to the terminal AM.
55
M040
Frequency monitoring
reference
60 Hz
50 Hz
0 to 590 Hz
Set the full-scale value when
outputting the frequency monitor
value to terminals FM, CA and AM.
56
M041
Current monitoring reference
Inverter
Rated current
Set the full-scale value when
outputting the output current
monitor value to terminals FM, CA
and AM.
866
M042
Torque monitoring reference
150%
0 to 400%
Set the full-scale value when
outputting the torque monitor value
to terminals FM, CA and AM.
290
M044
Monitor negative output
selection
0
0 to 7
Set the availability of output with a
minus sign for the terminal AM, the
operation panel display, or
monitoring via communication.
(Refer to page 5-204.)
291
D100
Pulse train I/O selection
0
Pulse train
input
(terminal JOG)
Pulse train
output
(terminal FM)
0
JOG signal
FM output
1
Pulse train input
FM output
10
JOG signal
High-speed pulse
train output
(50% duty)
11
Pulse train input
High-speed pulse
train output
(50% duty)
20
JOG signal
High-speed pulse
train output
(ON width fixed)
21
Pulse train input
High-speed pulse
train output
(ON width fixed)
100
Pulse train input
High-speed pulse
train output
(ON width fixed)
Output the pulse
train input
without changes.
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......