Basic operation
Basic operation procedure (JOG operation)
FR-F800
4 - 31
4.7.2
JOG operation from the operation panel
쑶
NOTE
Operate only while FWD or REV key is pressed.
Fig. 4-13:
Connection example for jog operation performed
from PU
I002433E
Example
쑴
Operation example: Operate at 5 Hz.
Operation
Screen at power-ON
The monitor display appears.
Changing the operation mode
Press
twice to choose the PUJOG operation mode. The monitor displays
, and [PU] indicator is lit.
Start
➔
acceleration
➔
constant speed
Keep pressing
or
. The frequency value on the indication increases in Pr. 16 "Jog acceleration/
deceleration time", and "
" (5.00 Hz) appears.
Deceleration
➔
stop
Release
or
. The frequency value on the indication decreases in Pr. 16 "Jog acceleration/deceleration
time", and the motor stops rotating with "
" (0.00 Hz) displayed.
Tab. 4-22:
JOG operation performed from PU
NOTES
To change the running frequency, change Pr. 15 "Jog frequency" (initial value "5 Hz").
To change the acceleration/deceleration time, change Pr. 16 "Jog acceleration/deceleration time"
(initial value "0.5 s").
Parameters referred to
Pr. 15
Jog frequency
=>
Pr. 16
Jog acceleration/deceleration time
=>
Operation panel
(FR-DU08)
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......