Parameters
(M) Monitor display and monitor output signal
FR-F800
5 - 195
Actual operation
time
1 h
23
H17
40223
Displays the cumulative time
since the inverter began running.
The number of times the monitor
value exceeded 65535 h can be
checked with Pr. 564.
This can be cleared with Pr. 171.
(Refer to page 5-202)
Motor load
factor
0.1%
24
H18
40224
Displays the output current
value as a percentage,
considering the inverter rated
current value as 100%.
Monitor value = output current
monitor value / inverter rated
current × 100 [%]
Cumulative
power
0.01 kWh/
0.1 kWh
25
H19
40225
Displays the cumulative energy
based on the output power
monitor.
This can be cleared with Pr. 170.
(Refer to page 5-202.)
Motor output
0.01 kW/
0.1 kW
34
H22
40234
Multiplies the output torque at
that time with the motor speed,
and displays the machine output
for the motor shaft end.
Trace status
1
38
H26
40238
Displays the trace status.
(Refer to page 5-437)
PLC function
user monitor 1
Accord-
ing to the
SD1215
setting
40
H28
40240
Displays the arbitrary monitoring
item using the PLC function.
Displays the following special
register values.
SD1216: Displays in No. 40
SD1217: Displays in No. 41
SD1218: Displays in No. 42
(Refer to the PLC Function
Programming Manual.)
PLC function
user monitor 2
41
H29
40241
PLC function
user monitor 3
42
H2A
40242
Station number
(RS-485
terminals)
1
43
H2B
40243
Displays which station number (0
to 31) can currently be used for
communication from the RS-485
terminal block.
Station number
(PU)
1
44
H2C
40244
Displays which station number (0
to 31) can currently be used for
communication from the PU
connector.
Station number
(CC-Link)
1
45
H2D
40245
Displays which station number (0
to 31) can currently be used for
CC-Link communication.
Displays "0" when the FR-A8NC is
not connected.
Energy saving
effect
Changea-
ble by pa-
rameter
setting.
50
H32
40250
Displays the energy saving effect
monitor.
Conversion to power saving,
average power saving, price
display, and percentage display
can be done using parameters.
(Refer to page 5-57.)
Cumulative
energy saving
51
H33
40251
PID set point
0.1%
52
H34
40252
Displays the set point, measured
value, and deviation under PID
control.
(Refer to page 5-362)
PID measured
value
0.1%
53
H35
40253
PID deviation
0.1%
54
H36
40254
Input terminal
status
—
55
40215
Displays input terminal ON/OFF
state of the inverter. (Refer to
page 5-201 for DU display.)
Output terminal
status
—
H10
40216
Displays output terminal ON/OFF
state of the inverter. (Refer to
page 5-201 for DU display.)
Types of
monitor
Unit
Pr. 52,
Pr. 774 to Pr. 776,
Pr. 992
RS-485
communica-
tion dedicat-
ed monitor
(hexadeci-
mal)
MODBUS
RTU real
time
monitor
Minus (-)
display
Description
Tab. 5-87:
Monitor description list (2)
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......