(T) Multi-Function Input Terminal Parameters
Parameters
5 - 276
Fault output (Pr. 573 = "2")
●
When the analog current input becomes 2 mA or lower, 4 mA input fault (E.LCI) will be activated
and the output is shut off.
●
PID control (reverse action)
Fault output after deceleration to stop (Pr. 573 = "3")
●
When the analog current input becomes 2 mA or lower, 4 mA input fault (E.LCI) will be activated
after the deceleration stop and the output is shut off.
●
When the analog current input is restored during the deceleration, it will accelerate again and
operate according to the current input.
●
PID control (reverse action)
I002650E
Fig. 5-130:
Fault output (Pr. 573 = 2)
I002651E
Fig. 5-131:
Fault output after deceleration to stop (Pr. 573 = 3)
STF
Output frequency
Set point (fixed)
Measured value
20 mA
4 mA
LF signal
PID signal
ALM signal
E.LCI occurs
Input current
decrease
Return
3 mA
2 mA
Time
STF
Output frequency
Set point (fixed)
Measured value
Input current
decrease
Decelerates as the input current is lost
After deceleration stop, E.LCI occurs
Return
3 mA
2 mA
Time
4 mA
20 mA
LF signal
PID signal
ALM signal