![Mitsubishi Electric FR-F800 Instruction Manual Download Page 670](http://html.mh-extra.com/html/mitsubishi-electric/fr-f800/fr-f800_instruction-manual_1811884670.webp)
(N) Operation via communication and its settings
Parameters
5 - 508
●
Model information monitor
Register
Definition
Read/write
Remarks
44001
Inverter type (1st and 2nd characters)
Read
Reading inverter type in ASCII code.
"H20" (blank code) is set for blank area.
Example:
For the "FR-F840-1 (FM type)",
H46, H52, H2D, H46, H38, H34, H30, H2D, H31,
H20...H20
44002
Inverter type (3rd and 4th characters)
Read
44003
Inverter type (5th and 6th characters)
Read
44004
Inverter type (7th and 8th characters)
Read
44005
Inverter type (9th and 10th characters)
Read
44006
Inverter type (11th and12th characters)
Read
44007
Inverter type (13th and 14th characters)
Read
44008
Inverter type (15th and 16th characters)
Read
44009
Inverter type (17th and 18th characters)
Read
44010
Inverter type (19th and 20th characters)
Read
44011
Capacity (1st and 2nd characters)
Read
Reading inverter capacity in ASCII code.
Data is read in increments of 0.1 kW, and
rounds down to 0.01 kW increments.
"H20" (blank code) is set for blank area.
Example:
0.75K..." 7" (H20, H20, H20, H20, H20, H37)
44012
Capacity (3rd and 4th characters)
Read
44013
Capacity (5th and 6th characters)
Read
Tab. 5-274:
Model information monitor
NOTE
When a 32-bit parameter setting or monitor item is read and the value to be read exceeds HFFFF,
HFFFF is returned.
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......