Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix:
PLAT
ID:
0522
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffles are in place and correctly installed, and that the server
cover is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Features
and specifications for more information).
3. Make sure that the heat sink for microprocessor n is installed correctly.
4. (Trained technician only) Replace microprocessor n. (n = microprocessor number)
•
80070202-0701ffff : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (SysBrd Vol Fault)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702020701ffff or 0x800702020701ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Voltage
SNMP Trap ID
1
CIM Information
Prefix:
PLAT
ID:
0522
User Response
1. Check the system-event log.
2. Check for an error LED on the system board.
3.
Replace any failing device.
398
HX3510-G, HX5510, HX5510-C, HX7510 Installation and Service Guide
Summary of Contents for HX3510-G
Page 1: ...HX3510 G HX5510 HX5510 C HX7510 Installation and Service Guide Machine Type 8695 ...
Page 6: ...iv HX3510 G HX5510 HX5510 C HX7510 Installation and Service Guide ...
Page 62: ...50 HX3510 G HX5510 HX5510 C HX7510 Installation and Service Guide ...
Page 102: ...90 HX3510 G HX5510 HX5510 C HX7510 Installation and Service Guide ...
Page 112: ...100 HX3510 G HX5510 HX5510 C HX7510 Installation and Service Guide ...
Page 1222: ...1210 HX3510 G HX5510 HX5510 C HX7510 Installation and Service Guide ...
Page 1238: ...1226 HX3510 G HX5510 HX5510 C HX7510 Installation and Service Guide ...
Page 1239: ......
Page 1240: ......