DC Power Electrical Safety Guidelines
DC Power Electrical Safety Guidelines
The following electrical safety guidelines apply to a DC-powered services gateway:
•
A DC-powered services gateway is equipped with a DC terminal block that is rated for the power
requirements of a maximally configured services gateway. To supply sufficient power, terminate the DC
input wiring on a facility DC source capable of supplying at least 30 A @ -48 VDC for the system. We
recommend that the 48 VDC facility DC source be equipped with a circuit breaker rated at
40 A (-48 VDC) minimum, or as required by local code. Incorporate an easily accessible disconnect device
into the facility wiring. In the United States and Canada, the -48 VDC facility should be equipped with
a circuit breaker rated a minimum of 125% of the power provisioned for the input in accordance with
the National Electrical Code in the US and the Canadian Electrical Code in Canada. Be sure to connect
the ground wire or conduit to a solid office (earth) ground. A closed loop ring is recommended for
terminating the ground conductor at the ground stud.
•
Run two wires from the circuit breaker box to a source of 48 VDC. Use appropriate gauge wire to handle
up to 40 A.
•
A DC-powered services gateway that is equipped with a DC terminal block is intended only for installation
in a restricted access location. In the United States, a restricted access area is one in accordance with
Articles 110-16, 110-17, and 110-18 of the National Electrical Code ANSI/NFPA 70.
NOTE:
Primary overcurrent protection is provided by the building circuit breaker. This
breaker should protect against excess currents, short circuits, and earth faults in accordance
with NEC ANSI/NFPA70.
•
Ensure that the polarity of the DC input wiring is correct. Under certain conditions, connections with
reversed polarity might trip the primary circuit breaker or damage the equipment.
•
For personal safety, connect the green and yellow wire to safety (earth) ground at both the services
gateway and the supply side of the DC wiring.
509
Summary of Contents for SRX 5800
Page 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Page 23: ......
Page 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Page 111: ...LEDs 112 ...
Page 121: ...Port and Interface Numbering 122 ...
Page 127: ...Port and Interface Numbering 128 ...
Page 161: ......
Page 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Page 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Page 205: ......
Page 261: ......
Page 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Page 365: ...Figure 143 Installing an SPC 366 ...
Page 367: ...368 ...
Page 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Page 423: ......
Page 457: ......
Page 473: ...475 ...
Page 476: ...Restricted Access Area Warning 478 ...
Page 483: ...485 ...
Page 496: ...Jewelry Removal Warning 498 ...
Page 499: ...Operating Temperature Warning 501 ...
Page 509: ...DC Power Disconnection Warning 511 ...
Page 513: ...DC Power Wiring Sequence Warning 515 ...
Page 516: ...DC Power Wiring Terminations Warning 518 ...
Page 519: ...DC Power Disconnection Warning 521 ...
Page 523: ...DC Power Wiring Sequence Warning 525 ...