NOTE:
If output power is not load-balancing correctly in the same zone on a services gateway
with a high-capacity AC or DC power supply module, connect two feeds and change the DIP
switch to 1 to boost the voltage on the power supply module.
Each High Capacity AC or DC power supply accepts two AC or DC feeds in two unique AC or DC
receptacles. It is possible to operate with one feed, but there is a reduction in the power supply output.
The DIP switch must be set according to the number of AC or DC feeds that are present for the power
supply.
Figure 156: AC Power Input Mode Switch
g006057
0
1
1
0
•
Position – 0 indicates that only one AC or DC feed is provided.
•
Position – 1 indicates that two AC or DC feeds are provided.
The following example shows what should be the DIP switch position based on the number of AC or DC
input feeds expected and connected to the PEM:
1. Issue the CLI show chassis power command and check how many feeds are connected.
The sample out put below is the output of a chassis with AC power supplies:
user@host
# run show chassis power
PEM 0:
State: Online
AC input: OK (2 feed expected, 2 feed connected)
Capacity: 4100 W (maximum 4100 W)
DC output: 798 W (zone 0, 14 A at 57 V, 19% of capacity)
452
Summary of Contents for SRX 5800
Page 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Page 23: ......
Page 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Page 111: ...LEDs 112 ...
Page 121: ...Port and Interface Numbering 122 ...
Page 127: ...Port and Interface Numbering 128 ...
Page 161: ......
Page 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Page 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Page 205: ......
Page 261: ......
Page 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Page 365: ...Figure 143 Installing an SPC 366 ...
Page 367: ...368 ...
Page 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Page 423: ......
Page 457: ......
Page 473: ...475 ...
Page 476: ...Restricted Access Area Warning 478 ...
Page 483: ...485 ...
Page 496: ...Jewelry Removal Warning 498 ...
Page 499: ...Operating Temperature Warning 501 ...
Page 509: ...DC Power Disconnection Warning 511 ...
Page 513: ...DC Power Wiring Sequence Warning 515 ...
Page 516: ...DC Power Wiring Terminations Warning 518 ...
Page 519: ...DC Power Disconnection Warning 521 ...
Page 523: ...DC Power Wiring Sequence Warning 525 ...