Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Function:
2-channel operation
Object
h
19,
20,
21,
27,
28,
29,
...34
Function
Channel 2 temperature value
Name
Rocker/button 1
1,2
Type
2 byte
DPT
9,001
Flag
C, -, -, T, -
3
Description
2-byte object to transmit value telegrams. This object is enabled if 2-channel
operation is activated with the function "Temperature value transmitter
(2-byte)" for channel 2.
Objects for full-surface operation with rocker function (with dimming, Venetian blind and
2-channel operation):
Function:
Full-surface operation
Object
h
2, 4,
6, 8,
10,
12,
14,
16
Function
Switching
Name
Rocker 1 full-
surface operation
1,2
Type
1-bit
DPT
1.xxx
Flag
C, (R), W,
T, -
3
Description
1-bit object for the transmission of switching telegrams (ON, OFF) when there
is full-surface operation of a control surface.
Function:
Full-surface operation
Object
h
2, 4,
6, 8,
10,
12,
14,
16
Function
Scene extension
Name
Rocker 1 full-
surface operation
1,2
Type
1 byte
DPT
18,001
Flag
C, -, -, T, -
3
Description
1-byte object for recalling or for storing one of 64 scenes max. from a scene
pushbutton sensor in case of full-surface operation of a control surface.
1: The number of rockers or buttons depends on the planned push-button sensor variant and
the push-button sensor extension module. Mixed operation of rocker or button functions in a
push-button sensor is possible on the basic module and the extansion module.
2: The objects have been described for rocker 1 or button 1 as an example. The objects for the
other rockers/buttons and for the module rockers are defined in the same way by shifting the
object number and changing the object name.
3: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
Page 48 of 309
Software "Room controller display compact module 146x11"
Object table