Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Function:
Basic setpoint shifting
Object
h
183,
243
Function
Preset setpoint shifting
Name
C.Input
Type
1 byte
DPT
6,010
Flag
C, (R), W,
-, -
1
Description
1-byte object for setting a basic setpoint shifting, e.g. via a controller
extension. The value of a counter value in the communication object is 0.5 K.
The value "0" means that no shift is active. The value is depicted in a double
complement in the positive and negative direction.
In case the limits of the value range are exceeded by the preset external
value, the controller will automatically reset the received value to the minimum
and maximum limits.
This object is only available in this way if relative setpoint presetting is
configured.
Object for command value limit
Function:
Command value limit
Object
h
186,
246
Function
Command value limit
Name
C.Input
Type
1-bit
DPT
1,001
Flag
C, (R), W,
-, -
1
Description
1-bit object for activating or deactivating the command value limit.
Objects for fan control
Function:
Fan controller
Object
h
188,
248
Function
Ventilation, automatic/manual
Name
C.Input
Type
1-bit
DPT
1,001
Flag
C, (R), W,
T, -
1
Description
1-bit object to change-over the operating mode of the fan controller
(configurable polarity). When the operating mode is changed over using a
button function, a telegram matching the current status is transmitted to the
bus.
Function:
Fan controller
Object
h
189,
249
Function
Ventilation, fan level 1-8
Name
C.Output
Type
1-bit
DPT
5,010
Flag
C, R, -,T, -
1
Description
1-byte object for value-guided activation of the fan levels. This object is only
available in this way when the fan control is to take place over 1 byte
(parameter-dependent).
1: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
Page 75 of 309
Software "Room controller display compact module 146x11"
Object table