Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Controller operation
Motion detection
Presence telegram
No telegram
Controller operation
Setpoint shift
Level value telegram
No telegram
Controller operation
Fan controller
Fan level telegram
No telegram
No function
No telegram
No telegram
Telegram reactions of the pushbutton sensor with respect to the target push-button function
o
Set the parameter "Reaction of pushbutton sensor at the beginning / end of disabling" to
"Reaction as disabling function 1 / 2 when pressed / released".
The device (TSM + TSEM) executes the function assigned to either of the two "virtual"
disabling functions. The disabling functions are internal button functions with independent
communication objects and independent parameters. Except for the status LED, the setting
possibilities available for disabling function 1 and disabling function 2 are the same as for
the buttons.
The respective configuration of the predefined disabling function will be executed. If no
function or no telegram is configuration in the disabling function on pressing or releasing of
a button, then there is also no reaction to disabling or to re-enabling.
Also, for this setting, Table 1 shows all possible telegram reactions of the push/button
sensor depending on the project design of the disabling function.
The telegrams are transmitted to the bus via the required communication object of the
disabling function.
Configuring the reaction during a disable
Irrespective of the behaviour shown by the push-button sensor at the beginning or at the end of
disabling, the control buttons can be separately influenced during disabling.
The disabling function must have been enabled in advance.
o
Set the parameter "Behaviour during active disabling" to "all buttons without function".
The device is then completely disabled during disabling. Pressing a button has no effect.
The status LEDs of the disabled buttons are without function (no button-press display
either). Only the "Always ON" or "Always OFF" state remains unaffected by the disabling
function.
o
Set the parameter "Behaviour during active disabling" to "all buttons behave like". Also, set
the parameters "All buttons with even / odd numbers behave during disabling like" to the
desired button number, module button number or disabling function.
All buttons behave as defined in the parameters for the two specified reference buttons of
the pushbutton sensor. For all control buttons with an even number (2, 4, 6, …) and for all
buttons with an odd number (1, 3, 5, …) it is possible to program not only different
reference buttons, but also identical reference buttons. The two "virtual" disabling functions
of the push button sensor can also be configured as a reference button.
The telegrams are transmitted to the bus via the communication objects of the specified
reference buttons. The status LEDs of the reference buttons are controlled according to
their function. The status LEDs of the disabled buttons are without function (no button-
press display either). Only the "Always ON" or "Always OFF" state remains unaffected by
the disabling function.
o
Set the parameter "Behaviour during active disabling" to "Individual buttons without
function". The buttons that will be disabled are defined on the parameter page "Disable -
Button selection" page.
Page 204 of 309
Software "Room controller display compact module 146x11"
Functional description