Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Effect on
Heating, basic level
Heating, additional level
The temperature limit can also be used
in a two-level feedback control with
basic and additional levels. It must then
be specified here to which level the limit
shall apply. Either the basic level or to
the additional level for heating can be
limited.
This parameter can only be set in two-
level control operation.
Maximum temperature,
underfloor heating
* 1 °C
20...
30
...70
The maximum limit temperature which
the underfloor heating system may
reach is specified here. If this
temperature is exceeded, the controller
switches the underfloor heating system
off using the command value. As soon
as the floor temperature has fallen 1 K
under the limit temperature, the
controller switches the command value
on again, assuming that this is intended
in the control algorithm. The 1 K
hysteresis is fixed and cannot be
changed.