Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
0 = static OFF
1 = static OFF /
0 = LED flashing
switching telegram can be evaluated in
such a way that the illumination flashes.
Time for automatic
switch-off
(Minutes)
0
...20
If the "Function of the labelling field
illumination" is set to "Automatic switch-
off", the delay before switch-off after the
last button-press can be configured
here.
Setting the delay time minutes.
Seconds
0...
3
...59
Setting the delay time seconds.
h
TSM - Operation concept
h
TSEM - Operation concept
Operation concept of
buttons 1 and 2
(The same parameters
are available for the
other control surfaces /
button pairs.)
Rocker function (rocker
1)
Button function
For each respectively opposing buttons,
it can be set whether they are to be
used combined as a rocker with a
common basic function or as two
buttons with separate functions.
Depending on this setting, the ETS
displays different communication objects
and parameter pages.
Depending on the parameter "Standard
operating/display function", this
parameter is preset to button function.
The following parameters are valid for: Standard display function (TSM) and standard display
function (TSEM).
h
Standard display function
Page of LED line
setpoint shift
none
Right
Left
This parameter defines whether the
device shows the status of the current
setpoint shift using four status LEDs and
the side of the device showing the
current setpoint shift. The device either
shows the current setpoint shift on the
right-hand side (status LEDs 2, 4, 6 and
8) or on the left-hand side of the device
(status LEDs 1, 3, 5 and 7). A positive
adjustment is represented by a red
illuminated status LED and a negative
Page 221 of 309
Software "Room controller display compact module 146x11"
Parameters