Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Basic heating and cooling
Basic heating and
additional cooling
Basic cooling and
additional heating
Additional heating and
cooling
level during heating and cooling.
However, under no circumstances is it
possible to use the basic and additional
levels simultaneously for a fan controller
within an operating mode.
This basic setting of this parameter
depends on the selected controller
operating mode.
Transmit heating and
cooling command
values to one common
object
Yes
No
If the parameter is set to "Yes", the
command value will be transmitted on a
shared object during heating or cooling.
This function is used, if the same
heating system is used to cool the room
in the summer and used to heat the
room in the winter.
This parameter is only visible with
"heating and cooling" mixed operating
mode, if applicable, with additional
levels.
Type of heating control
(if applicable, for basic
and additional stage)
Continuous PI control
Switching PI control (PWM)
Switching 2-point feedback
control (ON/OFF)
Selecting a feedback control algorithm
(PI or 2-point) with data format (1 byte or
1 bit) for the heating system
Type of heating (if
applicable, for basic and
additional level)
Hot water heater
(5 K / 150 min)
Underfloor heating
(5 K / 240 min)
Electric heating
(4 K / 100 min)
Fan convector
(4 K / 90 min)
Split unit (4 K / 90 min)
via control parameter
Adapting the PI algorithm to different
heating systems using predefined
values for the proportional range and
reset time control parameters.
With the "Using control parameters"
setting, it is possible to set the control
parameters in a manner deviating from
the predefined values within specific
limits.
This parameter is only visible if "Type of
heating control = Continuous PI control".
Proportional range
heating
(10 ... 127) * 0.1 K
10...
50
...127
Separate setting of the "Proportional
range" control parameter.
This parameter is only visible if "Type of
heating = via control parameter" and the
heating control type "PI control".
Reset time heating
(0 ... 255) * 1 min; 0 =
inactive
0...
50
...255
Separate setting of the "Reset time"
control parameter.
This parameter is only visible if "Type of
heating = via control parameter" and the
Page 261 of 309
Software "Room controller display compact module 146x11"
Parameters