Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
4.2.4.9 Disabling function
Configuration
With the 1-bit communication object "Disable buttons", the control surfaces on the TSM and
TSEM can be partly or completely disabled. During a disable, the rockers or buttons cannot
execute any functions or can execute, temporarily, another function.
An active disable applies only to the functions of the rockers or buttons. The functions of the
status LED, the scene function, temperature measurement and the alarm signalling are not
affected by the disabling function.
The disabling function and the pertaining parameters and communication objects are enabled if
the parameter "Disabling function ?" is set to "Yes" on the "Disabling" parameter tab.
You can parameterize the polarity of the disabling object. In case of polarity inversion (disabled
= 0 / enabled = 1), the disabling function is not activated immediately after a reset or after ETS
programming (object value = "0"). There must first be an object update "0" until the disabling
function will be activated.
Telegram updates from "0" to "0" or from "1" to "1" on the "button disabling" object remain
without effect.
The disabling function can be selected to include all or only some buttons of the basic and
extension modules. If not all buttons should be blocked with the disabling function, set the
parameter "Assignment of the buttons for disabling function" to "Individual buttons assigned". In
this case, an additional parameter page "Disabling - button selection" is shown. For each
potentially possible button (basic and extension modules), a selection can be made on this page
as to whether it should correspondingly change its performance when disabling is activated (set
parameter "Button..." to "Yes") or continue to execute its standard function (set parameter
"Button..." to "No").
Defining the disabling function
o
On parameter page "Disabling", set the parameter "Disabling function?" to "Yes".
The communication objects "Disabling function 1...", "Disabling function 2..." and "Disable
buttons - disable" are shown, as are additional parameters and parameter pages.
o
Specify the polarity of the disabling object.
o
Select those buttons, which should be affected by the disabling function, with the
parameter "Assignment of the buttons for disabling function" and, as needed, with the
parameters on the page "Button selection".
Configuring the reaction at the beginning and end of a disable
If the disabling function is used, the reaction of the pushbutton sensor on activation and
deactivation of the disabling function can be set separately in the parameterisation (parameter
"Reaction of pushbutton sensor at the beginning / end of disabling"). In this connection it is
irrelevant which of the control surfaces is influenced and possibly also locked by disabling. The
push-button sensor always shows the configured behaviour.
The disabling function must have been enabled in advance.
o
Set the parameter "Reaction of pushbutton sensor at the beginning / end of disabling" to
"No reaction".
The push-button sensor (TSM + TSEM) shows no reaction at the beginning and at the end
of disabling. The sensor only adopts the state as provided for by the "Behaviour during
active disabling".
o
Set the parameter "Reaction of pushbutton sensor at the beginning / end of disabling" to
"Internal scene recall scene 1 …8".
The push-button sensor (TSM + TSEM) recalls one of the up to 8 internal scenes. Scene
storage is not possible.
o
Set the parameter "Reaction of push-button sensor at the beginning / end of disabling" to
"Reaction as button >> X << / >> Y << when pressed / released".
Page 202 of 309
Software "Room controller display compact module 146x11"
Functional description