Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
push-button sensor reaches the lower
limit of the adjustment range (0 or 0 %)
or the upper limit (255 or 100 %) during
value adjustment, the adjustment will be
stopped automatically by the sensor.
If the value adjustment with overflow is
programmed (setting "Yes") and if the
push-button sensor reaches the lower or
the upper limit, it will transmit the value
of this range limit and then add a pause
the duration of which corresponds to two
levels. Thereafter, the push-button
sensor transmits a telegram with the
value of the other range limit and
continues the value adjustment in the
same direction.
h
Button 1, value transmitter, 2-byte
Function
Temperature value
transmitter
Brightness value
transmitter
Value transmitter
(0...65535)
A button configured as "Value
transmitter 2 byte" permits selecting
whether the values to be transmitted are
to be interpreted as temperature values
(0 °C to 40 °C), as brightness values
(0 lux to 1500 lux) or as integers
(0 to 65535). The following parameters
and their settings depend on this
selection.
Temperature value
(0...40 °C)
0...
20
...40
This parameter defines the object value
when the button is pressed.
This is only visible if "Function =
Temperature value transmitter"!
Brightness value
0, 50,...
300
...1450,
1500 lux
This parameter defines the object value
when the button is pressed.
This is only visible if "Function =
Brightness value transmitter"!
Value (0...65535)
0
...65535
This parameter defines the object value
when the button is pressed.
This is only visible if "Function = Value
transmitter (0...65535)"!
Value adjustment by
long button-press
enabled
Disabled
If value adjustment by long button-press
is enabled, the ETS shows further
parameters.
Value adjustment begins, when the
button is held down for more than 5 s. In
this case, the respective status LED
flashes as a sign that a new telegram
has been transmitted.
Page 241 of 309
Software "Room controller display compact module 146x11"
Parameters