Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
represents one piece of status
information. The controller supports five
of these status information items. In the
"Controller general" setting, various
status signals of the controller are output
as a collective signal via an object of 1
byte. Each bit represents one piece of
status information.
Sending command
value for heating and
cooling to a shared
object
Yes
No
If the parameter is set to "Yes", the
command value will be transmitted on a
shared object during heating or cooling.
This function is used, if the same
heating system is used to cool the room
in the summer and used to heat the
room in the winter. This parameter is
only visible with "heating and cooling"
mixed operating mode, if applicable,
with additional levels.
Type of heating control
continuous PI control
switching PI control (PWM)
2-point feedback control
Selecting a feedback control algorithm
(PI or 2-point) with data format (1-byte
or 1-bit) for the heating system. This
parameter is only visible if the operating
mode "Heating" or "Heating and cooling"
is configured and when the command
values for heating and cooling are
transmitted via two separate objects.
Type of cooling control
continuous PI control
switching PI control (PWM)
2-point feedback control
Selecting a feedback control algorithm
(PI or 2-point) with data format (1-byte
or 1-bit) for the cooling system. This
parameter is only visible if the operating
mode "Cooling" or "Heating and cooling"
is configured and when the command
values for heating and cooling are
transmitted via two separate objects.
Type of control
continuous PI control
switching PI control (PWM)
2-point feedback control
Selecting a feedback control algorithm
(PI or 2-point) with data format (1 byte or
1 bit). This parameter is only visible if
the operating mode "Heating and
cooling" is configured and when the
command values for heating and cooling
are transmitted via two separate objects.
Output of the heating
variable
normal (under current,
this means opened)
inverted (under current, this
means closed)
At this point, it is possible to specify
whether the command value telegram
for heating is output normally or in
inverted form. This parameter is only
visible if the operating mode "Heating"
or "Heating and cooling" is configured
and when the command values for
heating and cooling are transmitted via
Page 285 of 309
Software "Room controller display compact module 146x11"
Parameters