Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Function:
Controller extension
Object
h
70,
76
Function
Current setpoint shifting
Name
RNST
n
.Button fct.
Input
Type
1 byte
DPT
6,010
Flag
C, (R), W,
-, A
1
Description
1-byte object used by the extension unit for receiving the current setpoint shift
of the room temperature controller.
x ≤ 0 ≤ y (0 = no shift active); integral numbers
The possible range of values (x to y) is fixed by the setpoint adjusting range to
the 'upper limit' or to the 'lower limit' (configurable) in combination with the
level value on the room temperature controller.
Function:
Controller extension
Object
h
166,
226
Function
Controller status
Name
RNST
n
.Display fct.
Input
Type
1 byte
DPT
Not
defined
Flag
C, (R), W,
-, A
1
Description
1-byte object used by the extension unit for receiving the current state of
operation of the controller. Status LEDs that can be used to indicate a status
independently of a button function can display one of the various information
units which are grouped in this byte (bit-oriented evaluation). This object is
enabled when the "Controller status" parameter is set to "KNX-conformant".
Function:
Controller extension
Object
h
166,
226
Function
KNX status operating mode
Name
RNST
n
.Display fct.
Input
Type
1 byte
DPT
Not
defined
Flag
C, (R), W,
-, A
1
Description
1-byte object used by the extension unit for receiving the current state of
operation of the controller. Status LEDs, that can be used to display a status
independently of a button function, can display one of the various pieces of
information which are grouped in this byte (bit-oriented evaluation). This object
is enabled when the "Controller status" parameter is set to "KNX-conformant".
Function:
Controller extension
Object
h
176,
236
Function
Command value for heating
0%...100%
Name
RNST
n
.Display fct.
Input
Type
1 byte
DPT
5,001
Flag
C, -,W, -,
U
1
Description
1-byte object to output the continuous command value of the heating mode. In
two-level heating mode, command value output for the basic heating. This
object is only available in this way if the type of feedback control is configured
to "Continuous PI control".
Function:
Controller extension
Object
h
176,
236
Function
Command value for heating
On/Off
Name
RNST
n
.Display fct.
Input
Type
1 byte
DPT
1,001
Flag
C, -,W, -,
U
1
Description
1-bit object to output the switching command value of the heating mode. In
two-level heating mode, command value output for the basic heating. This
object is only available in this way if the type of feedback control is configured
to "Switching 2-point feedback control".
1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
Page 81 of 309
Software "Room controller display compact module 146x11"
Object table