Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
-
Bit 1: Comfort mode extension
-
Bit 2: Status of the presence detector ( presence = 1 / no presence = 0)
-
Bit 3: Status of the presence button (presence = 1 / no presence = 0)
-
Bit 4: Window status (Window open = 1 / Window closed = 0)
-
Bit 5: Additional level active
-
Bit 6: Heat protection active
-
Bit 7: Dew point alarm active
Description of bit-oriented status messages of the room temperature controller (active = ON)
Normal/ forced operation: Active if the normal operation is activated and inactive if the forced
operation is activated.
Comfort mode extension: Active if the comfort mode extension is activated.
Presence detector: Presence: Active if presence via sensor is activated.
Presence button: Presence: Active if presence via button is activated.
Window open: Active if window contact is active.
Additional level active: Active if the additional level is activated.
Heat protection active: Active if the heat protection is activated.
active dew point alarm: Active if the dew point alarm is activated.
Below is a breakdown of the status objects listed separately for the KNX compliant controller
status...
Controller status: KNX compliant
The object "KNX controller status" groups 5 different information units in a bit-oriented way in
two bytes. For this reason it is important to select in the "Status LED on with" parameter which
information is to be indicated, i.e. which bit is to be evaluated.
The following can be selected...
-
Bit 0: Controller fault
-
Bit 8: Heating / cooling (heating = 1 / cooling = 0)
-
Bit 12: Dew point alarm active
-
Bit 13: Frost protection temperature undershot!
-
Bit 14: Heat protection temperature exceeded!
Description of bit-oriented KNX compliant status messages of the room temperature controller
(active = ON)
Bit 0: Active if controller fault.
Bit 8: Active in heating mode and inactive in cooling mode.
Bit 12: Active in active dew point operation.
Bit 13: Active if frost protection temperature is undershot.
Bit 14: Active if heat protection temperature is exceeded.