Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
4.2.5.7 Parameter group "Alarm"
Description
Values
Comment
h
Push-button sensor -> Alarm signalling
Alarm signal display
activated
deactivated
This parameter can be used to enable
alarm signal displaying.
When alarm signalling is enabled, the
ETS displays further parameters and up
to two further communication objects.
Polarity of the alarm
signalling object
Alarm when ON and
Alarm reset when OFF
Alarm when OFF and
Alarm reset when ON
The alarm signalling object is used as
an input for activating or deactivating
alarm signal displaying.
If the object value corresponds to the
"Alarm" state, all status LEDs and the
operation LEDs flash with a frequency
of approx. 2 Hz.
If the setting is "Alarm when OFF and
alarm reset when ON", the object must
first be actively written by the bus with
"0" to activate the alarm after a reset.
An alarm signal is not stored so that the
alarm signalling is generally deactivated
after a reset or after programming with
the ETS.
Reset alarm signalling
by a button actuation?
Yes
No
If this parameter is set to "Yes", active
alarm signal displaying can be
deactivated by a button actuation on the
push-button sensor.
This button function does not cause the
configured function of the pressed
button to be executed. Only after then
next button-press will the configuration
of the button be evaluated and a
telegram be transmitted to the bus, if
applicable.
If "No" has been selected, alarm
signalling can only be deactivated via
the alarm signalling object. A button-
press will always execute the configured
button function.
Use the alarm
acknowledge object?
Yes
No
If alarm signalling can be deactivated by
a button actuation, this parameter
defines whether an additional alarm
acknowledge telegram is to be
transmitted to the bus via the separate
object "Alarm signalling acknowledge"
after triggering by this button-press.
A telegram can, for instance, be sent via
this object to the "Alarm signalling"
Page 298 of 309
Software "Room controller display compact module 146x11"
Parameters