Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
-
"Transmit individual state"
The 1 bit status object "Controller status, ..." contains the status information selected by the
"Single status" parameter. Meaning of the status signals:
"Comfort mode active" -> Active if operating mode "Comfort " or a comfort extension "" is
activated.
"Standby mode active" -> active if the "standby " operating mode is activated.
"Night-mode active" -> active if the "night " operating mode is activated.
"Frost/heat protection active" -> active if the "frost/heat protection" operating mode is
activated.
"Controller disabled" -> Active if controller disable is activated (dew point mode).
"Heating / cooling" -> Active if heating is activated and inactive if cooling is activated.
Inactive if controller is disabled.
"Controller inactive" -> Is active in the following parameter settings: "Operating mode =
Heating and cooling" and "Switchover between heating and cooling = Automatic" when the
measured room temperature lies within the dead zone. This status information is always "0"
for the individual "Heating" or "Cooling" operating modes. In the "Heating and cooling"
operating mode, the status information is also "0", if the switchover between heating and
cooling takes place using an object. Inactive if controller is disabled.
"Frost alarm" -> Is active if the detected room temperature reaches or falls below +5 °C.
This status signal will have no special influence on the control behaviour.
i
Upon a reset, the status objects will be updated after the initialisation phase. After this,
updating is performed cyclically every 30 seconds in parallel with the command value
calculation of the controller command values. Telegrams are only transmitted to the bus
when the status changes.
Additional controller status
The additional controller status is a 1-byte object, in whose value various information is
collected in orientated to bits. In this way, controller statuses, which are not available via the
'normal' 1-bit or 1-byte controller status, can be displayed on other KNX/EIB devices or
processed further (see Table 11). For example, controller extensions can evaluate the
additional status information, in order to be able to display all the necessary controller status
information on the extension display.
The 1-byte object "Status signal addition" is a pure visualisation object, which cannot be written.
i
The object "Status signal addition" is only visible when the parameter "Status controller" is
configured to "Controller general".
Bit of the
status telegram
Meaning on "1"
Meaning on "0"
0
Normal operating mode
Forced operating mode
1
Comfort extension active
No comfort extension
Page 140 of 309
Software "Room controller display compact module 146x11"
Functional description