Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
However, this is only if the parameter
"Setpoint temperature limit in cooling
operation" is then set to "Only difference
to outdoor temperature" or "Max.
setpoint temperature and difference to
outdoor temperature".
Max. setpoint
temperature in cooling
operation
20°C...
26°C
...35°C
This parameter defines the maximum
setpoint temperature in Comfort mode
with an active setpoint temperature limit.
This parameter is visible only if setpoint
temperature monitoring is enabled.
However, this is only if the parameter
"Setpoint temperature limit in cooling
operation" is then set to "Only max.
setpoint temperature" or "Max. setpoint
temperature and difference to outdoor
temperature".
Change-over between
heating and cooling
Automatic
Via object (heating/cooling
change-over)
In a configured mixed mode it is
possible to switch over between heating
and cooling.
With "Automatic": Depending on the
operating mode and the room
temperature, the change-over takes
place automatically.
With "Via object (heating/cooling
change-over)": The change-over takes
place only via the object "Heating /
cooling change-over".
With automatic setpoint presetting this
parameter is permanently set to "Via
object (heating/cooling switch-over)"!
Heating / cooling
operating mode after a
reset
Heating
Cooling
Operating mode before
reset
The preset operating mode for after the
return of the bus voltage is specified
here.
Only visible if "Change-over between
heating and cooling = via object"!
Automatic
heating/cooling
transmission switchover
On changing the
operating mode
On changing the output
value
Here, it is possible to specify when a
telegram is transmitted automatically
onto the bus via the object "Heating /
cooling change-over".
Only visible if "Change-over between
heating and cooling = automatic".
Cyclical transmission
heating/cooling switch-
over
(0...255) * 1 min;
0 = inactive
0
...255
This parameter specifies whether the
current object status of the "Heating /
cooling change-over" object should be
output cyclically to the bus on an
automatic change-over. The cycle time
can be set here. The "0" setting
deactivates the periodic transmission of
Page 280 of 309
Software "Room controller display compact module 146x11"
Parameters