has elapsed. A setting of "0" will effect
the immediate activation of the frost/heat
protection mode when the window is
open. The window status will be in effect
in the heating and in the cooling mode.
This parameter is only visible if the
parameter "Frost/heat protection" is set
to "Via window status".
Automatic frost
protection temperature
drop
Off
0.2 K / min
0.3 K / min
0.4 K / min
0.5 K / min
0.6 K / min
You can use the "automatic frost
protection temperature drop" parameter
to set the maximum temperature drop in
K/min for switching over to the frost
protection mode. After the time preset
by the "frost protection period in
automatic mode" parameter has
elapsed, the regulator will return into the
mode which was set before frost
protection. Re-triggering will not be
possible.
Frost protection period,
automatic mode
(minutes)
1 ...
20
... 255
This parameter defines the length of the
frost protection when frost protection is
activated automatically.
Output rotation angle
(only if "Output of
command value"
=normal)
Disabled
enabled
This parameter is only visible when the
operating mode is set to "Heating and
cooling", the parameter "Send command
value for heating and cooling to a
shared object" is set to "YES", the type
of control is set to "Continuous PI
control" and the parameter "Output
command value" is set to "Normal...".
It defines whether rotation angle
conversion of the Heating and Cooling
command value output is to take place
or not. If this parameter is enabled, five
additional parameters appear, along
with the KNX communication object
"Rotation angle"
min rotation angle for
cooling,(0...255) * 1°
0...
0
...255
This parameter specifies the minimum
size of the rotation angle for cooling.
max rotation angle for
cooling, (0...255) * 1°
0...
30
...255
This parameter specifies the maximum
size of the rotation angle for cooling.
Rotation angle for
deadband, (0...255) * 1°
0...
45
...255
This parameter determines the rotation
angle at which the deadband is set.
Within the deadband, neither heating
nor cooling will take place.