Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Permanently apply
change to basic setpoint
shift
No
Yes
In addition to the setting of individual
temperature setpoints via the ETS, the
user is able to shift the basic setpoint
within a settable range anytime via local
control or via the basic setpoint object,
either using the display buttons or with
the "Setpoint shift" push button function,
if this is configured to a function button
of the push button sensor. Whether a
basic setpoint shifting only affects the
currently active operating mode or
whether it influences all other setpoint
temperatures of the remaining operating
modes is determined by this parameter.
In the "Yes" setting, the shift of the basic
setpoint carried out affects all operating
modes. The shifting is maintained even
after switching-over the operating mode
or the heating/cooling mode or
readjusting the basic setpoint.
In the "No" setting, the basic setpoint
shift carried out is in effect for only as
long as the operating mode or
heating/cooling mode has not changed
or the basic setpoint is maintained.
Otherwise the setpoint shift will be reset
to "0".
Changing of the basic
temperature setpoint
value via bus
deactivated
Approve
Here, it is possible to specify if it is
possible to change the basic setpoint via
the bus. In the "Approve" setting, the
"Basic setpoint" object is visible in the
ETS.
Accept modification of
the basic temperature
setpoint value
permanently
No
Yes
One has to distinguish between two
cases, defined by this parameter, if the
basic setpoint has been modified (via
local control or via the object):
In the "Yes" setting, the controller saves
the basic setpoint permanently in the
EEPROM. The newly adjusted value will
overwrite the basic temperature
originally configured via the ETS after a
reset! This is the only way to keep the
adjusted basic setpoint even after
change-over of the operating mode or
after a reset.
In the "No" setting, the basic setpoint,
which was set on the room temperature
controller or received via the object,
stays only temporarily active in the
current operating mode. In case of a bus
voltage failure or following a change-
over to another operating mode (e.g.
Page 275 of 309
Software "Room controller display compact module 146x11"
Parameters