Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Comfort followed by Standby), the basic
setpoint set via local control or received
via the object will be discarded and
replaced by the value which was
originally configured in the ETS.
Frost protection setpoint
temperature
(7...40) * 1 °C
7
...40
This parameter specifies the setpoint
temperature for frost protection. The
parameter is only visible in "Heating" or
"Heating and cooling" operating modes
(if necessary with additional levels).
Heat protection setpoint
temperature
(7...45) * 1 °C
7...
35
...45
This parameter specifies the setpoint
temperature for heat protection. The
parameter is only visible in "Cooling" or
"Heating and cooling" operating modes
(if necessary with additional levels).
Dead band position
symmetrical
asymmetrical
The comfort setpoint temperatures for
"Heating and cooling" operating modes
are derived from the basic setpoint in
consideration of the adjusted deadband.
The deadband (temperature zone for
which there is neither heating nor
cooling) is the difference between the
comfort setpoint temperatures.
Symmetrical setting: the deadband
preset in the ETS plug-in is divided in
two parts at the basic setpoint. The
comfort setpoint temperatures are
derived directly from the basic setpoint
resulting from the half deadband (Basic
setpoint - 1/2 deadband = Heating
comfort temperature or Basic se
1/2 deadband = Cooling comfort
temperature).
Asymmetrical setting: with this setting
the comfort setpoint temperature for
heating equals the basic setpoint! The
preset deadband is effective only from
the basic setpoint in the direction of
comfort temperature for cooling. Thus
the comfort set-temperature for cooling
is derived directly from the comfort
setpoint for heating.
The parameter is only visible in "Heating
and cooling" operating modes (if
necessary with additional levels).
Deadband between
heating and cooling
(0...127) * 0.1 K
0...
20
...127
The comfort setpoint temperatures for
heating and cooling are derived from the
basic setpoint in consideration of the
adjusted deadband. The deadband
(temperature zone for which there is
Page 276 of 309
Software "Room controller display compact module 146x11"
Parameters