Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
4.2.5.8 "Display" parameter group
Description
Values
Comment
h
Display
Backlighting
Always off
always On
Switch on through button-
press
Switch on in night mode
Switch on through button-
press or Night mode
Switch on through
switching object
Switch on through inverted
switching object
Switch on through button-
press or switching object
Switch on through button-
press or inv. switching
object
Switch on through value
object (0%...100%)
Switch on through button-
press or value object
(0%...100%)
The backlighting can be permanently on
or off or alternatively be switched
according to events. If the lighting is
switched on by pressing a operating
area (rocker or button), the device
switches the lighting off automatically
when the switch-off time configured in
the ETS elapses. The switch-off time is
retriggered each time a control surface
is actuated.
If the lighting is to be switched on in the
"Night" operating mode, the lighting
remains switched on continuously when
night mode is active. Switching on by
pressing a button or via the operating
mode "Night" always takes place using
the brightness value configured in the
ETS or specified locally in the menu
level.
When the backlighting is switched by the
1-bit communication object (alternatively
to the 1-byte object), the lighting
remains switched on continuously
according to the switching value (not
inverted: "0" = OFF / "1" = ON; inverted:
"0" = ON" / "1" = OFF). Here the switch-
on brightness is defined by the display
brightness value configured in the ETS
or specified locally in the menu level.
In the case of activation by the value
object the lighting is dimmed in
accordance with the received value
("1...254") or actuated to the maximum
("255"). The value "0" switches the
lighting off completely.
Lighting activation by operating a
operating area can be combined with
switching or dimming via the
corresponding objects. In this case the
control via the communication objects
has a higher priority. The lighting is
switched on automatically by pressing a
control surface, and is only switched off
again when the switch-off time
configured in the ETS elapses, if the
lighting is to be switched off via the
corresponding communication object
(object value "OFF" or "0"). Switching on
by pressing a button always takes place
using the brightness value configured in
the ETS or specified locally in the menu
level. In addition, the lighting can also be
switched or dimmed by the
communication objects, independently
Page 300 of 309
Software "Room controller display compact module 146x11"
Parameters