Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Yes
No
storing it while the system is running,
this parameter must be set to "Yes".
Allow transmission?
Yes
No
If the state of an actuator group is to
remain unchanged during the recall of a
scene, this parameter can be set to
"No". In this case, the push-button
sensor does not transmit a telegram via
the scene output concerned during the
recall of the scene. The scene output is
deactivated for this scene.
Scene 1
Transmit delay
(1 … 1200 * 100 ms)
(0 = deactivated)
0
...1200
When the push-button sensor sends the
telegrams to the various scene outputs,
it can insert a presettable waiting time of
2 min. max. before each telegram. The
bus load can be reduced by this. In this
way, it is possible to have certain
illumination switched on only after the
shutters are really closed.
If no delay is selected ("0" setting), the
push-button sensor sends the output
telegrams with maximum speed. With
this setting it may happen in some cases
that the telegram sequence is not
compatible with output numbering.
Scene output 2...8 like
Scene output 1!
h
Scene output 1 ... 8 for data type "Value / Venetian blind position (0...100%)"
Scene output 1
Scene 1
Value / position of
Venetian blind
(0 … 100 %)
0
...100
Here, it is possible to predefine the
value of scene output 1 when scene 1 is
recalled via the extension object.
This parameter is only visible if "Data
type (scene output 1) = Value / Venetian
blind (0...100%)".
Allow save?
Yes
No
If the user is to be given the possibility of
changing the value of the scene and of
storing it while the system is running,
this parameter must be set to "Yes".
Allow transmission?
Yes
No
If the state of an actuator group is to
remain unchanged during the recall of a
scene, this parameter can be set to
"No". In this case, the push-button
sensor does not transmit a telegram via
the scene output concerned during the
recall of the scene. The scene output is
deactivated for this scene.
Page 295 of 309
Software "Room controller display compact module 146x11"