4.2.4.5 Room temperature measurement
Basic principles
The room temperature controller possesses an integrated temperature sensor, using which the
room temperature can be detected. The TSEM offers a second option for room temperature
measurement, as it also possesses an internal temperature sensor. Alternatively (e.g. if the
room temperature controller has been installed in an unfavourable location or operates in
difficult conditions, for example, in a moist atmosphere) or in addition (e.g. in large rooms or
halls), a permanently wired remote sensor can be connected to the TSM for temperature
detection. Thus, the device offers a total of three methods for room temperature measurement,
which can run in parallel.
The three methods for room temperature measurement can be configured on the "Room
temperature measures -> TSM", "Room temperature measurement -> TSEM" and "Room
temperature measurement -> Remote sensor" parameter pages. For each method, the
temperature can be detected by the internal sensor, a received temperature value or the
combination of measured temperature value (internal sensor) and received temperature value.
The "Received temperature value" setting enables a communication object for receiving the
temperature.
When choosing the installation location of the controller or the external sensors, the following
points should be considered:
-
The controller or temperature sensor should not be used in multiple combinations,
especially together with flush-mounted dimmers.
-
Do not install the temperature sensor in the area of large electrical consumers (avoid heat
influences).
-
The push button sensor should not be installed in the vicinity of radiators or cooling
systems.
-
The temperature sensor should not be exposed to direct sun.
-
The installation of sensors on the inside of an outside wall might have a negative impact on
the temperature measurement.
-
Temperature sensors should be installed at least 30 cm away from doors, windows or
ventilation units and at least 1.5 m above the floor.
i
Room temperature measurement by the device is active, irrespective of the "Room
temperature control" or "Controller extension" functions and can thus be used
independently (e.g. for simple measurement and display of a room temperature without
control).
i
A deviation may occur in the measured temperature after a device reset or after switching
on the background illumination of the display. Comparative measurements for the
calibration of the room temperature measurement should take place approx. 30 minutes
after a device reset or switching on the display.