Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Only the individually specified buttons are locked during disabling. The other control
buttons remain unaffected by disabling. The status LEDs of the disabled buttons are
without function (no button-press display either). Only the "Always ON" or "Always OFF"
state remains unaffected by the disabling function.
o
Set the parameter "Behaviour during active disabling" to "Individual buttons behave like".
The buttons that will be disabled are defined on the parameter page "Disable - Button
selection" page. Continue to configure the parameters "All assigned left / right buttons
behave like" to the required button number, module button number or disabling function.
Only the individually specified buttons behave as defined in the parameters of the two
specified reference buttons of the pushbutton sensor. Different or identical reference
buttons can also be configured for all the right (2, 4, 6, …) and all the left buttons
(1, 3, 5, …). The two "virtual" disabling functions of the push button sensor can also be
configured as a reference button. The buttons that will be disabled are defined in the
parameters on the "Disable - buttons selection" page.
The telegrams are transmitted to the bus via the communication objects of the specified
reference buttons. The status LEDs of the reference buttons are controlled according to
their function. The status LEDs of the disabled buttons are without function (no button-
press display either). Only the "Always ON" or "Always OFF" state remains unaffected by
the disabling function.
i
If a button evaluation is taking place at the time of activation / deactivation of a disabling
function, this function is aborted immediately and with it also the pertaining button function.
It is first necessary to release all buttons before a new button function can be executed if so
permitted by the state of disabling.
Page 205 of 309
Software "Room controller display compact module 146x11"
Functional description