Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
4.2.4.11 Delivery state
The delivery state defines the functions of the device when it is connected to the KNX but has
not been programmed with application data by the ETS.
This condition persists until the application is programmed into the device.
The text NEU appears in the device display, as soon as the device is supplied with bus voltage
and no button has been pressed. In the delivery state, the device makes four displays available,
which are switched through by pressing button 1. Changing the display also changes the
display brightness. The information is shown in the following order in the display of the TSM:
-
NEU / Display brightness: 100 %
-
Actual temperature (TSM) / Display brightness: 20 %
-
Actual temperature (remote sensor) / Display brightness: 20 %
-
Segment test / Display brightness: 100 %
The first actuation of button 1 causes the display to switch to the actual temperature measured
by the TSM, which is shown in °C. When button 1 is pressed again, the actual temperature
measured by the remote sensor is shown, providing that a remote sensor is connected to the
TSM. After the third button-press of button 1, all the available segments in the display are
activated. This segment test provides the installation engineer with an overview of the
designable display information and button icons at a display brightness of 100%. The next time
a button is pressed, the display begins again with the NEU text.
In the delivery state of this device, the eight status LEDs execute the function of an actuation
display. In so doing, the status LEDs light up for the length of the actuation of the corresponding
button. The colour of the status LED changes in the following order with each press of a button:
-
Red
-
Green
-
Blue
Using the top two status LEDs 1 and 2, the device can also indicate that an application which
cannot run has been programmed into its memory by the ETS. The status LEDs 1 and 2 then
change colour between red, blue and off at a frequency of around 0.75 Hz. Applications cannot
run if they are not intended for use with the device in the ETS product database.
The top two status LEDs flash even if the TSM application program has been removed by the
ETS.
In both cases, the room controller display compact module is not operational.
Page 207 of 309
Software "Room controller display compact module 146x11"
Functional description