Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Function:
Command value
Object
h
173,
233
Function
Cmd. value, add. heating
(PWM)
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, (R), -,T,
-
1
Description
1-bit object to output the continuous PWM command value for additional
heating in two-level operation. This object is only available in this way if the
type of feedback control is configured to "Switching PI control (PWM)".
Function:
Command value
Object
h
173,
233
Function
Cmd. value, additional
heating
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, (R), -,T,
-
1
Description
1-byte object to output the switching command value for additional heating in
two-level operation. This object is only available in this way if the type of
feedback control is configured to "Switching 2-point feedback control".
Function:
Command value
Object
h
173,
233
Function
Cmd. value, add. level
Name
C.Output
Type
1 byte
DPT
5,001
Flag
C, (R), -,T,
-
1
Description
1-byte object to output the combined continuous command value for additional
level in two-level operation. This object is only available in this way if the
command values for heating and cooling mode are output to a shared object
(parameter-dependent). The type of feedback control must also be configured
to "Continuous PI control".
Function:
Command value
Object
h
173,
233
Function
Cmd. value, add. level
(PWM)
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, (R), -,T,
-
1
Description
1-bit object to output the combined switching PWM command value for
additional level in two-level operation. This object is only available in this way
if the command values for heating and cooling mode are output to a shared
object (parameter-dependent). The type of feedback control must also be
configured to "Switching PI control (PWM)".
Function:
Command value
Object
h
173,
233
Function
Cmd. value, add. level
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, (R), -,T,
-
1
Description
1-bit object to output the combined switching command value for additional
level in two-level operation. This object is only available in this way if the
command values for heating and cooling mode are output to a shared object
(parameter-dependent). The type of feedback control must also be configured
to "Switching 2-point feedback control".
1: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
Page 70 of 309
Software "Room controller display compact module 146x11"
Object table