Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Control" can recall or store up to 64
scenes by their numbers. The parameter
defines the scene number to be
transmitted when the button is pressed.
Scene number
(1 … 8)
1
...8
This parameter defines the number of
the internal scene which is recalled or
stored when a button is pressed.
h
Button 1, 2-channel operation
h
Button 1, controller extension
Function takes effect
Controller extension 1
Controller extension 2
The button function "Controller
extension" can either affect Controller
extension 1 or 2. The precondition for
this is that the selected controller
extension is enabled in the parameter
node "Room temperature control".
Function
Operating mode
switch-over
Forced oper. mode
switchover
Presence button
Setpoint shift
A controller extension can optionally
switch over the operating mode with
normal or high priority, change the
presence state or change the current
room temperature value. With regard to
the setting of this parameter, the ETS
shows further parameters.
Operating mode when
the following button is
pressed
Comfort mode
Standby mode
Night mode
Frost/heat protection mode
Comfort mode ->
Standby mode ->
Comfort mode ->
Night mode ->
Standby mode ->
Night mode ->
Comfort mode ->
Standby mode ->
Night mode ->
If the controller extension is to change
over the operating mode of the
connected room temperature controller
with normal priority, the extension can –
when operated – either switch on a
defined operating mode or change over
between different operating modes.
In order for this change to work properly,
the controller extension should request
the current state of the extension objects
after a reset or after re-programming
(set parameter under "General" to
"Value request from controller extension
= Yes").
This parameter is only visible if
"Function = operating mode switchover"!
Forced operating mode
when the following
button is pressed
Auto
(Normal operating mode
change-over)
If the controller extension is to change
over the operating mode of the
connected room temperature controller
with high priority, the extension can –
Page 244 of 309
Software "Room controller display compact module 146x11"
Parameters