Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
4.2.4.2.2 Display control
Change-over of the display
Up to 17 pieces of display information (actual temperature, setpoint temperature, outdoor
temperature, any temperature) can be optionally displayed on the LC display of the device with
the room temperature controller icons. (see page 89). The individual pieces of information are
shown separately in the numeric display.
It is possible to switch between the information automatically after set times or, independently of
this, in a controlled manner by pressing a button on the device:
-
Change-over by time:
If more than one piece of display information is configured in the ETS in the parameter
node "Display", then the display must be switched over during operation. The ETS
parameter "Cyclical change of display functions" specifies the display time of a piece of
information. The next piece of information is displayed when this time has elapsed. When
the last piece of information has been reached, there is a changeover to the first piece of
information.
-
Change-over through button-press
In addition to the cyclical change, the indication can also be switched by pressing a button
on the device. To do this it is possible to configure a button for the "Change in the display
reading" function. This configuration is performed in the parameter block of the respective
button (see chapter 4.2.4.6.9. "Change in the display reading" function). This function can
be configured for any desired buttons on the room controller display compact module and
optionally also for buttons on the extension module.
When a button is pressed, depending on the button parameterisation either the next or the
previous display information is called up in accordance with the cyclical change. With this
setting the display information specified according to the configuration in the "Display"
parameter node can be switched directly.
Alternatively it is also possible to call up a particular piece of information immediately
independently of the display information of the cyclical change (e.g. button function "Recall
display information 1"). It is not assumed here that the indication called up in this manner is
in fact integrated into the cyclical change. After a piece of information is called up by
pressing a button, the indication is retained until the time for the cyclical change has
elapsed.
i
In the parameter node "Display -> General -> General information -> Display
n
", it is also
possible to set that no information is displayed using the parameter "Display information
n
".
In this case, the normal depiction of the display is dark (only the designed button function
icons are displayed). It is then only possible as necessary to call up individual display
information by pressing a button using the button function "Change in the display reading".
The indication called up in this manner then remains temporarily visible in the display
depending on the time configured for the cyclical change.
i
The piece of display information last called up by the cyclical change or by a button press is
overridden and overwritten in the display if the device is operated locally in another way
(e.g. temporary setpoint temperature display in the case of setpoint shift, menu level).
Page 93 of 309
Software "Room controller display compact module 146x11"
Functional description