Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
-
For the rocker functions Dimming, Venetian blind (operation concept "Long – Short or
Short") and 2-channel operation, full-surface rocker operation can also be evaluated. With
full-surface operation, switching telegrams and scene recall requests can be triggered on
the KNX in addition to and independently of the configured rocker function.
-
The switching function permits the following settings: reaction after pressing and/or
releasing, switch on, switch off, and toggle.
-
The dimming function permits the following settings: times for short and long actuation,
dimming in different levels, telegram repetition on long press, transmission of stop telegram
after end of press.
-
The shutter control permits the following settings: four different operation concepts with
times for short and long press and slat adjustment.
-
The 1-byte and 2-byte value transmitter function permits the following settings: selection of
the value range (0 … 100 %, 0 … 255, 0 … 65535, 0 … 1500 lux, 0 … 40 °C), value on
button-press, value change on sustained button-press with different step widths, optional
overflow on reaching the end of a value range.
-
The controller extension function permits the following settings to operate an external room
temperature controller: operating mode change-over with normal and high priority, defined
selection of an operating mode, change between different operating modes, change of
presence status, setpoint shift.
-
The rockers or buttons can be disabled via a 1-bit object. The following settings are
possible: polarity of the disabling object, behaviour at the beginning and at the end of
disabling. During an active disable, all or some of the rockers / buttons can have no
function, can perform the function of a selected button or execute one of two presettable
disabling functions.
-
A delay to the automatically transmitted communication objects of the controller external
after a device reset can be configured. The delay time is automatically produced by the
subscriber address (physical address).
LED functions
-
The status LED can light up in red, green or blue according to choice. An automatic colour
change is also possible depending on the function. When switched-off, the status LEDs can
shine in a designed colour, creating an orientation light.
-
The brightness of the status LED can be set to five levels. Through night reduction, the
brightness of the status LED can be reduced at night using a communication object.
-
Possible status LED functions include, among others, "always OFF", "always ON", "button-
press display", "Status display", "2-colour status display", "Activation via separate LED
object", "Operating mode display", "Controller status display", "Comparator without/with
sign (1 byte)" and "Fan controller display".
-
The operation LED of the TSEM can be permanently on or off or alternatively be switched
via a communication object. The operation LED can light up in red, green or blue according
to choice.
-
All status LEDs of the device can flash simultaneously in the event of an alarm. The
following settings are possible: Value of alarm signalling object for the states alarm / no
alarm, alarm acknowledge by actuation of a button, transmission of the acknowledge signal
to other devices.
Page 41 of 309
Software "Room controller display compact module 146x11"
Scope of functions