Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Object for additional command value output, PWM additional cooling
Function:
Command value
Object
h
179,
239
Function
PWM cmd. value, add.
cooling
Name
C.Output
Type
1 byte
DPT
5,001
Flag
C, (R), -,T,
-
1
Description
1-byte object to output the internal continuous command value of a PWM
feedback controller for additional cooling in two-level operation. This object is
only available in this way if the type of feedback control is configured to
"Switching PI control (PWM)". In addition to the switching 1 bit command value
of the PWM, the calculated continuous command value of the controller can
also be transmitted to the bus and displayed, e.g. in a visualisation.
Object for outputting the setpoint temperature
Function:
Set temperature
Object
h
180,
240
Function
Set temperature
Name
C.Output
Type
2 byte
DPT
9,001
Flag
C, (R), -,T,
-
1
Description
2-byte object for the output of the current temperature setpoint. Depending on
the operating mode, the possible range of values is limited by the configured
frost protection and/or heat protection temperature.
The temperature value is always output in the format "°C".
Object for basic setpoint shift (only for relative setpoint presetting)
Function:
Basic setpoint shifting
Object
h
182,
242
Function
Current setpoint shifting
Name
C.Output
Type
1 byte
DPT
6,010
Flag
C, R, -,T, -
1
Description
1-byte object for giving feedback on the current setpoint shifting. The value of
a counter value in the communication object is 0.5 K. The value "0" means
that no shift is active. The value is depicted in a double complement in the
positive and negative direction.
This object is only available in this way if relative setpoint presetting is
configured.
1: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
Page 74 of 309
Software "Room controller display compact module 146x11"
Object table