Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Function:
Room temperature measurement
Object
h
270
Function
Measured value
Name
S. Temperature
RS output
Type
2 byte
DPT
9,001
Flag
C, (R), -,T,
-
Description
2-byte object for the display of the determined actual temperature. The actual
temperature is either determined by the internal sensor, a received
temperature value or by a combination of both measurement methods. The
output temperature value takes the configured value for calibration into
account, as well as the measured value formation between the temperature
values. Possible value range: -99.9 °C to +99.9 °C / Measurement range of
internal temperature sensor: 0 °C to +40 °C. Depending on the configuration,
the temperature value is output in the display of the TSM in the format "°C" or
"°F".
This communication object is assigned to the room temperature measurement
of the remote sensor (RS). It is only enabled when the room temperature
measurement of the RS is enabled.
Function:
Room temperature measurement
Object
h
271
Function
External temperature
Name
S.Temperature RS
input
Type
2 byte
DPT
9,001
Flag
C, -, W, -, -
1
Description
2-byte object for coupling an external KNX room temperature sensor. Thus
cascading of multiple temperature sensors for room temperature
measurement. Possible range of values: -99.9 °C to +99.9 °C. The
temperature value must always be specified in the format "°C".
This communication object is assigned to the room temperature measurement
of the remote sensor (RS). It is only enabled when the room temperature
measurement of the RS is enabled and when a "received temperature value"
is involved in temperature detection.
Function:
Room temperature measurement
Object
h
274
Function
Non-balanced measured
value
Name
S. Temperature
RS output
Type
2 byte
DPT
9,001
Flag
C, (R), -,T,
-
Description
2-byte object for the display of the determined actual temperature. The actual
temperature is either determined by the internal sensor, a received
temperature value or by a combination of both measurement methods. The
output value does not take the configured value for calibration into account.
Internal to external measured value formation is taken into account. Possible
value range: -99.9 °C to +99.9 °C / Measurement range of internal
temperature sensor: 0 °C to +40 °C. Depending on the configuration, the
temperature value is output in the display of the TSM in the format "°C" or "°F".
This communication object is assigned to the room temperature measurement
of the remote sensor (RS). It is only enabled when the room temperature
measurement of the RS is enabled.
1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
Page 61 of 309
Software "Room controller display compact module 146x11"
Object table