Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Function:
Temperature display
Object
h
279
Function
Display of setpoint
temperature
Name
D.Input
Type
2 byte
DPT
9,001
Flag
C, -, W, -, -
1
Description
2-byte object for receiving a setpoint temperature. The setpoint temperature
can be shown on the display.
Function:
Temperature display
Object
h
280
Function
Display of outdoor
temperature
Name
D.Input
Type
2 byte
DPT
9,001
Flag
C, -, W, -, -
1
Description
2-byte object for receiving an outdoor temperature. The outdoor temperature
can be shown on the display.
Function:
Temperature display
Object
h
281,
282,
283
Function
Display of any temperature
(1-3)
Name
D.Input
Type
2 byte
DPT
9,001
Flag
C, -, W, -, -
1
Description
2-byte objects for receiving any temperature values. The temperatures can be
shown on the display.
Function:
Recalling display information
Object
h
284
Function
Recall fixed display
information
Name
D.Input
Type
1-bit
DPT
1,001
Flag
C, -, W, -, -
1
Description
1-bit object, using which previously configured display information is recalled
on the display.
Function:
Recalling display information
Object
h
284
Function
Recall variable display
information
Name
D.Input
Type
1 byte
DPT
5,010
Flag
C, -, W, -, -
1
Description
1-byte object, using which the up to 17 items of configurable display
information can be recalled.
"1" telegram: Recall display 1
"2" telegram: Recall display 2
...
"17" telegram: Recall display 17
1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
Page 56 of 309
Software "Room controller display compact module 146x11"
Object table