4.2.5.4 Parameter group "Room temperature measurement"
Description
Values
Comment
The product database of the device contains three independent blocks for temperature
measurement. Up to three temperatures can be determined in parallel, depending on whether
the TSM is alone, is combined with a TSEM and/or with a connected remote sensor. Each
temperature measurement can be performed by the internal sensor or, optionally, by a received
temperature value. Combined temperature recording (internal received temperature
value) can also be configured.
h
TSM
h
TSEM
h
Remote sensor
Room temperature
measurement
enabled
Disabled
On the parameter pages "TSM", "TSEM"
and "Remote sensor", this parameter
decides whether the module is used for
room temperature measurement.
Measurement can take place using the
internal sensor of the module/the remote
sensor or a temperature value received
via KNX, as well as with a combination
of both methods. When room
temperature measurement is enabled,
the parameters and objects are also
enabled.
The precondition for room temperature
measurement using a remote sensor is
that a remote sensor is connected to the
device.
Temperature detection
through
internal temperature
sensor
received temperature value
internal sensor and
received temperature value
This parameter specifies which sensor is
used for room temperature
measurement.
With the setting "Internal sensor" only
the temperature sensor integrated in the
device detects the room temperature.
With the setting "Received temperature
value", only a KNX/EIB temperature
sensor (e.g. controller extension)
coupled via the "External temperature"
object detects the room temperature.
With the setting "Internal sensor and
received temperature value", the
KNX/EIB temperature sensor (e.g.
controller extension) integrated into the
device and coupled via the "External
temperature" object detects the room
temperature.
Determination of
measured value from
internal / external ratio
10% to 90%
20% to 80%
30% to 70%
40% to 60%
50% to 50%
The weighting of the measured
temperature value for the internal and
external sensors is specified here. That
results in an overall value, which will be
used for the further interpretation of the
Page 287 of 309
Software "Room controller display compact module 146x11"
Parameters