Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Switching object display
information
Recall display information 1
Recall display
information 2
...
Recall display information
17
The communication object "Recall fixed
display information" recalls the display
information set here when it is written
with a "1" telegram.
Cyclical changeover of
display information (s)
1...
10
...60
This parameter specifies after how long
a changeover of display information
takes place on the display. There is no
cyclical change of the display
information, if a piece of display
information is recalled via the
communication object.
Display button function
icons
Yes
No
In the display, a button function icon can
be assigned to each button. This
parameter enables the parameter page
"Button function icons" for project design
of the button function icons.
Button function icons are only available
in the CD and LS series!
Controller 1 temporary
setpoint display for
setpoint shift
Yes
No
Optionally the setpoint of the respective
current operating mode can be shown
automatically in the display if a setpoint
shift is performed using the buttons of
the device ("Setpoint shift" button
function). The setpoint temperature is
then displayed temporarily for 5 s in °C
or °F, and overwrites the normal display
(actual temperature, etc.). The setpoint
display for a setpoint shift is activated
when this parameter is set to "Yes".
With the setting "No" the temporary
display is inactive, meaning that in case
of a setpoint shift only the line graphic of
the display is activated, but the
temperature value is not also displayed
automatically.
The temporary setpoint value display is
only possible when controller is active
with relative setpoint specification!
Controller 2 temporary
setpoint display for
setpoint shift
Yes
No
Optionally the setpoint of the respective
current operating mode can be shown
automatically in the display if a setpoint
shift is performed using the buttons of
the device ("Setpoint shift" button
function). The setpoint temperature is
then displayed temporarily for 5 s in °C
or °F, and overwrites the normal display
Page 303 of 309
Software "Room controller display compact module 146x11"
Parameters