Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
"Only max. setpoint temperature"
setting: In this setting, no setpoint
temperatures are permitted in Cooling
mode related to the Comfort, Standby
and Night modes, which are greater
than the maximum setpoints configured
in the ETS. The maximum temperature
setpoint is specified by the "Max.
setpoint temperature in cooling
operation" parameter. With an active
limit, no larger setpoint can be set in
cooling operation, e.g. by a basic
setpoint change or a setpoint shift.
However, heat protection is not
influenced by the setpoint temperature
limit.
"Max. setpoint temperature and
difference to outdoor temperature"
setting: This setting is a combination of
the two above-mentioned settings. In the
downward direction, the setpoint
temperature is limited by the maximum
outdoor temperature difference, whilst in
the upward direction, the limit is made
by the maximum setpoint. The maximum
setpoint temperature has priority over
the outdoor temperature difference. This
means that the controller keeps on
raising the setpoint temperature
upwards according to the difference to
the outdoor temperature configured in
the ETS until the maximum setpoint
temperature or the heat protection
temperature is exceeded. Then the
setpoint is limited to the maximum value.
Activation of the
setpoint temperature
limit in cooling operation
via object
No
Yes
A setpoint limit enabled in the ETS can
be activated or deactivated as
necessary using a 1-bit object. For this,
this parameter can be set to "Yes". In
this case, the controller only takes the
setpoint limit into account, if it has been
enabled via the object "Cooling setpoint
temp. limit" ("1" telegram). If the
limitation is not enabled ("0" telegram),
the cooling setpoint temperatures are
not limited.
This parameter is visible only if setpoint
temperature monitoring is enabled.
Difference to outdoor
temperature in cooling
operation
1 K...
6 K
...15 K
This parameter defines the maximum
difference between the setpoint
temperature in Comfort mode and the
outdoor temperature with an active
setpoint temperature limit.
This parameter is visible only if setpoint
temperature monitoring is enabled.
Page 279 of 309
Software "Room controller display compact module 146x11"
Parameters