• For CO alarm notification, model PG9913 or PG9933 shall be enrolled on the system (zone type
is 24h CO). Both CO detectors provide T4 CO alarm signal independent of the control unit and
meet the 24 hour normal standby period followed by the 12 hour alarm period requirements.
The control panel provides T4 audible CO alarm for at least 5 minutes following 24 hour
normal standby.
• For UL Residential Fire applications, latching troubles shall be enabled (Section [019], Option 2
is ON).
• For UL Residential Fire applications, if a repeater is required, two of the model PG9920 shall be
used for proper signal routing.
• For Fire and CO applications, a RM-1(C) or RM-2 power loop supervision relay shall be
connected to Aux Power Output to report wiring faults if it is used for powering fire/CO
detection devices (for wiring information see manual 29009812).
Note:
For UL Residential Fire applications compliant with UL985 6th edition, the following
guidelines shall be respected when the equipment is used as a combination alarm system for
fire and burglary protection:
• Fire alarm detection devices shall not be powered from the same AUX output (control panel,
zone expander, power supply) as burglary alarm initiating devices.
• Power supply wiring for Fire Alarm Detection devices (Smoke Detectors, CO Detectors) shall
be connected to the control panel AUX output (located on the main control panel board
assembly).
• Power supply wiring for Burglary Alarm Initiating devices (Motion detectors, magnetic
contacts, glass break detectors, etc.) shall be connected to the compatible Power Supply
Module AUX outputs (located on the power supply module board assembly e.g. HSM2300,
HSM2204) or expander module AUX outputs located on the expander module board assembly
(e.g. HSM2108, HSM2208).
Note:
The DACT communicator for this product has no line security.
• For Fire and CO applications, RM-1(C) or RM-2 power loop supervision relay shall be connected
to Aux Power Output to report wiring faults if it is used for powering fire/CO detection devices.
• Telephone Line Monitoring (TLM) shall be enabled (section [015], option 7 shall be ON).
Note:
This product is programmed to perform 5 (min.) to 10 (max.) attempts for
communication of an event to the supervising station. If unsuccessful, a Fail To
Communicate (FTC) trouble is generated.
• Test transmission cycle shall be set for monthly transmission (refer to section [351]).
Note:
For ULC Residential/Commercial installations set for daily test transmission.
• Section [377][004] default time is programmed for 04:45am (0445). The panel generates a
random test transmission time within a +/- 60 minute window.
• Wireless Supervision window shall be set to 4 hrs for Fire Installations (Wireless Programming,
section [804]>[802] shall be programmed with the value 16).
• Wireless Supervision window shall be set to 4 hrs for Burglary Installations only (Wireless
Programming, section [804]>[802] shall be programmed with the value 96).
• RF Jam detection shall be enabled (refer to Wireless Programming (section [804][801], option
00 shall be OFF).
• New Alarms will Disconnect 2-way Audio (section [022], option 6 OFF).